• Any Questions? Call Us: 91 33 2231 8646
  • Skype: Rieindia
Get social with us!

M30 Power Analyzer

.


M30 Power Analyzer

Salient Features
  • A powerful power analyzer with data logger
  • 2 Programable Alarm Contacts
  • Energy Pulse Outputs - 2 Nos
  • Large LCD Screen
  • User configurable demand intergration period
  • Rs 485 computer interface
  • Display of complete harmonic spectrum - 2- 31th separately voltage & current THD V%, THD I%
Technical Specifications
Harmonic Measurement 2- 31th separately voltage & current THD V%, THD I%
Operating Voltage 230V AC * ± 10% : 50/60 Hz
Network Type 3 – phase / 4-wire(Star)
3 – phase / 3-wire(Delta)
Voltage Class 0.5
Current Class 0.5
Frequency Class 0.1
Active Power Class 1
Reactive Power 3-Phase / 3-Wire (Aron) Class 2
Current Transformer Ratio 1…2000 (programmable)
Voltage Transformer Ratio 1,0…4000,0 (programmable)
Measurement Range
Voltage 1.0-4000,0 kV
Current 5 mA – 10000 A
Frequency 45.0 – 65.0 Hz
Power 0 – 4000 M (W, VAr, VA)
Energy 0 – 99 999 999 kWh , kVArh
Power Consumption
Burden < 1 VA (Current burden),
Demand Time 1 – 60 min. (programmable)
Communication Interface MODBUS RTU (RS-485)
Baud Rate 1200 – 38400 bps
Address 1 – 247
Parity no. odd, even
Alarm Contact Output 1 / Output 2 : 2 NO Relay : 5 A, 1250 VA (resistive)
Energy Pulse Output Output 3 : Active Energy Pulse Output (1 kWh…50MWh / pulse) – NPN Transistor
Output 4 : Reactive Energy Pulse Output (1 kVArh…50MVArh / pulse) – NPN Transistor
Switch Period Min. 1 sec. (100…2500 msec. pulse width)
Operation Current Max. 50 mA
Operation Voltage 5…24 V DC. max. 30 V DC
Analog output (optional) 4 – 20 mA
Display 3.6″ LCD with Backlight, 12mm Height
Data Logging Selectable 28 parameters with Time Stamp (15000 records)
Memory 1 MB Internal Memory